Loop Flow Decomposition

Every branch flow in a meshed network is the sum of a tree component (scheduled, radial) and a loop component (circulating, unscheduled). The loop component is the holonomy of the voltage angle connection around each fundamental cycle of the network graph.

dim(cycle space) = |E| − |V| + 1 = 8  ·  f_loop = γ / Σx  ·  γ = ∮ dθ

λ = 0 (base)λ = 0.6λ = 1.2
Circulating power9741 MW26.6% of transmitted

Network — branch loop fraction(green = low loop, red = high loop, amber = selected cycle)

● Generator bus· Load/transit bus→ Flow direction

Fundamental cycles(8 co-tree chords)

Branch flow decomposition — all 46 branches

Sort by:
BranchTotal (MW)Tree (MW)Loop (MW)Loop %
11→12XFMR-129.0-668.6539.6418.3%
12→13XFMR-129.9409.7-539.6415.5%
4→14-494.646.4-541.0109.4%
26→28-388.0-796.7408.6105.3%
26→29-393.015.6-408.6104.0%
16→17583.71186.2-602.5103.2%
28→29-408.60.0-408.6100.0%
3→18-896.4-1714.7818.291.3%
17→18912.21730.5-818.289.7%
17→27-328.6-112.8-215.765.7%
26→27356.7572.4-215.760.5%
25→26-410.5-194.8-215.752.6%
10→13-984.4-1462.4478.148.6%
3→41495.22155.4-660.244.2%
22→23-53.9-75.922.040.9%
14→15-1608.8-1006.3-602.537.5%
15→16-1612.0-2214.5602.537.4%
10→111634.41156.3478.129.3%
2→3602.0443.9158.026.3%
2→25-928.1-712.4-215.723.2%
5→8-10.6-12.62.119.4%
6→7-376.7-432.355.614.8%
7→8-400.1-344.5-55.613.9%
9→39-462.9-405.2-57.712.5%
8→9-462.9-405.2-57.712.5%
1→39566.9509.257.710.2%
1→2-576.1-518.5-57.710.0%
4→51984.82104.0-119.26.0%
5→61995.32112.5-117.15.9%
13→14-1114.2-1052.7-61.55.5%
16→24-450.5-472.522.04.9%
23→24481.3503.4-22.04.6%
6→11-1763.4-1701.8-61.53.5%
16→21-676.5-654.5-22.03.3%
21→22-703.9-681.9-22.03.1%
16→19-1072.0-1072.00.00.0%
2→30XFMR-250.0-250.00.00.0%
6→31XFMR4135.44135.40.00.0%
10→32XFMR-650.0-650.00.00.0%
19→20XFMR-440.0-440.00.00.0%
19→33XFMR-632.0-632.00.00.0%
20→34XFMR-508.0-508.00.00.0%
22→35XFMR-650.0-650.00.00.0%
23→36XFMR-560.0-560.00.00.0%
25→37XFMR-540.0-540.00.00.0%
29→38XFMR-830.0-830.00.00.0%